Luminaire selection chart

Luminaire selection

A B C D E F G H I K L M N O P R S T U V W


Application

Protection rating

Regulations

Recommended product groups
(with exemplary references)

Remarks

A

Agricultural facilities

IP44

1) 3) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

In case dust occurs: IP54. Where applicable, premises posing a fire hazard. In case of animal husbandry consider ammonia resistance (see chapter “Chemical safety” ).

Air halls for storage

IP 20

1)

Diffuser luminaires Nextrema⋅⋅⋅, Duroxo⋅⋅⋅

Protection rating dependent on stored goods, in case dust occurs: IP50. In case of VDUs avoid reflex formation.

Archive rooms

IP20

1)

Diffuser luminaires: 3331⋅⋅⋅, Arimo Slim D CDP⋅⋅⋅

In case dust occurs: IP50. In case of VDU workspaces consider luminance limitation

Automobile washing rooms

IP54

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Duroxo⋅⋅⋅

Direct contact of the luminaire with cleaning agents can lead to embrittlement of diffuser fasteners etc. (see chapter “Chemical safety” ). Cleaning with jet water: IPx5, with pressure washers: IPx9, consider ambient temperature.

Automobile workshops

IP20

1) 12)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅ , Continuous-line luminaires: E-Line⋅⋅⋅, C-Line⋅⋅⋅, Coriflex⋅⋅⋅

In case of cleaning with jet water: IPx5, with pressure washers: IPx9. Stand-by lighting must be planned for in case of workspaces with particular hazards (also see Chapter “Emergency lighting”). In case of contact with fats and oils, luminaire covers made of PMMA are recommended.

B

Badminton halls

IP20

1)
12)

Diffuser luminaires: Actison⋅⋅⋅ with PMMA cover

Special luminaire placement, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”)

Bakeries

IP40

1) 2) 3) 12)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

In wet areas IP44, in case of cleaning with splash water IPx4, with jet water: IPx5, with pressure washers: IPx9. Where applicable, in rooms with flour silos IP54. Consider ambient temperature, plan safety lighting for workspaces with particular hazards (also see Chapter “Emergency lighting”).

Banks, teller windows/booking halls

IP20

1) 12)

Diffuser luminaires: Arimo Slim CDP⋅⋅⋅, Belviso Active⋅⋅⋅, louvre luminaires: Arimo Slim MRX⋅⋅⋅, work zone luminaires, if applicable: Belviso S⋅⋅⋅, Offset S⋅⋅⋅, Lateralo⋅⋅⋅, Luceos Slim⋅⋅⋅, Lunexo⋅⋅⋅, Parelia⋅⋅⋅, Bicult⋅⋅⋅

In case of VDU workspaces consider luminance limitation. Light accents increase the perceived value of the lighting, possibly lighting with colour-changing dynamics, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Basket weaving plant: bast, reeds, reed, straw

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Bath and laundry facilities

IPx4

1) 2)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Bathrooms and shower rooms, general

IP20

1) 4)

Diffuser luminaires: Acuro⋅⋅⋅, Solvan Flow C⋅⋅⋅, Polaron IQ⋅⋅⋅, Onplana⋅⋅⋅, Inplana⋅⋅⋅, Arimo Sky⋅⋅⋅, Arimo Slim CDP⋅⋅⋅

Outside Zone 0, 1 und 2.

Bathrooms and shower rooms, zone 0

IPx7

1) 4)

Cleaning with pressure washers: IPx9

Bathrooms and shower rooms, zone 1

IPx4

1) 4)

LED luminaires, protection class III

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Bathrooms and shower rooms, zone 2

IPx4

1) 4)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Beer and wine cellars

IPx1

1) 2)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

In case of cleaning with splash water IPx4, with jet water: IPx5, with pressure washers: IPx9.

Blackboards

IP 20

1)

Louvre and diffuser luminaires: 504⋅⋅⋅

Utilise luminaires with asymmetrical or narrow-angle light distribution, consider glare limitation.

Boiler houses

IPx1

1) 2)

Weather-proof luminaires, Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, consider ambient temperature.

Business premises (salesrooms)

IP20

1) 12)

Downlights: Inplana⋅⋅⋅, Onplana⋅⋅⋅, Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅, Diffuser and louvre luminaires: Arimo Slim MRX ⋅⋅⋅, Arimo Sky⋅⋅⋅, Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Belviso Active⋅⋅⋅, Accent luminaires

In case dust occurs: IP50. In case of VDU workspaces consider luminance limitation, light accents increase the perceived value of the lighting, possibly lighting with colour-changing dynamics, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

C

CAD rooms

IP 20

1)

work zone luminaires: Bicult⋅⋅⋅, Belviso S⋅⋅⋅, Offset S⋅⋅⋅, Lateralo⋅⋅⋅, Luceos Slim⋅⋅⋅, Lunexo⋅⋅⋅, Parelia⋅⋅⋅

Consider luminance limitation, brightness control recommended.

Canteen kitchens

IPx4

1) 2)

Weather-proof luminaires: Fidesca BS⋅⋅⋅, Nextrema⋅⋅⋅, Aragon⋅⋅⋅, 713⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, consider ambient temperature, in case of cleaning with aggressive cleaning agents, consider chemical resistance (see Chapter “Chemical safety”).

Cellar, heated and ventilated

IP20

1)

Diffuser luminaires: 3331⋅⋅⋅, Weather-proof luminaires: Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅

In case dust occurs IP50.

Cellar, unheated and unventilated

Px1

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅

Humid room.

Cellar, wine and beer

IPx1

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

In case of cleaning with splash water IPx4, with jet water: IPx5, with pressure washers: IPx9.

Cinema halls

IP20

1) 10) 12)

Wall-mounted luminaires: Polaron IQ⋅⋅⋅, Downlights: Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅ , Accent luminaires

Light accents increase the perceived value of the lighting. Emergency lighting of escape routes for 3 hour length of operation, where applicable anti-panic lighting (also see Chapter “Emergency lighting”)

Classrooms, blackboards

IP 20

1)

504⋅⋅⋅

Utilise luminaires with asymmetrical or narrow-angle light distribution, consider glare limitation.

Classrooms, general

IP 20

1)

3331⋅⋅⋅, Solvan Flow C⋅⋅⋅, Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Belviso Active⋅⋅⋅; Arimo Slim CDP ⋅⋅⋅, Luceos Slim⋅⋅⋅, Lunexo⋅⋅⋅

Consider glare limitation.

Classrooms, handicrafts

IP 20

1)

Diffuser luminaires: 3331⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard, when indicated.

Classrooms, music

IP 20

1)

Diffuser luminaires: 3331⋅⋅⋅, Deca⋅⋅⋅, Polaron IQ⋅⋅⋅, Arimo Slim CDP ⋅⋅⋅

Take noise level into consideration, luminaire louvres and loose components as well as ceiling components can be excited into resonance vibrations.

Cold-storage rooms, frozen storage rooms

IPx1

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Duroxo⋅⋅⋅

Particularly in case of short time operation LED-luminaires are recommended. Consider temperature specifications from the instruction sheet. In case of very deep temperatures use specified luminaires.

Combing and carding, textiles

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Concert halls, music schools

IP20

1) 10) 12)

Diffuser luminaires: 3331⋅⋅⋅, Polaron IQ⋅⋅⋅, 74R⋅⋅⋅, 74Q⋅⋅⋅

Take noise level into consideration, luminaire louvres and loose components as well as ceiling components can be excited into resonance vibrations, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Cork processing

IP50

1) 3)

Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Corridors, staircases

IP20

1) 12)

Downlights, Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅, Diffuser luminaires: 3331⋅⋅⋅, Wall-mounted luminaires: 74R⋅⋅⋅, 74Q⋅⋅⋅, 748⋅⋅⋅, Polaron IQ⋅⋅⋅

In case of increased occurrence of dust IP50 in the hand area, utilise diffuser luminaires and/or lamp with protective tubing. Avoid glare and irritations at stairs through correct lighting, LED luminaires preferred (in particular in case of automatic switching systems with short operating duration)

D

Dairies

IPx4

1) 2)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Data archive and data acquisition rooms

IP20

1)

Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Arimo Slim⋅⋅⋅, Fidesca SD⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅, work zone luminaires, if applicable: Parelia⋅⋅⋅

In case dust occurs IP50, VDU-compliant illumination required.

Data centres (see Data acquisition)

IP20

1)

Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Arimo⋅⋅⋅, Fidesca SD⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅, work zone luminaires, if applicable: Parelia⋅⋅⋅

In case dust occurs IP50, VDU-compliant illumination required.

Drying rooms

IP50

1) 3)

Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

E

EEG, ECG, EMG rooms

IP20

1) 7)

Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Belviso Active⋅⋅⋅, Arimo Slim CDP ⋅⋅⋅, Arimo Sky⋅⋅⋅

Illumination level and light colour differing dependent on the type of examination, in case of VDU workspaces consider luminance limitation. Where applicable, dimmable luminaires.

Event rooms

IP20

1) 10) 12)

Wall-mounted luminaires: 3331⋅⋅⋅, Polaron IQ⋅⋅⋅, 74R⋅⋅⋅, 74Q⋅⋅⋅, Downlights: Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅ , Accent luminaires Scenatic Point 905⋅⋅⋅

In case of VDU workspaces consider luminance limitation. Light accents increase the perceived value of the lighting, possibly lighting with colour-changing dynamics. Emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Event tents, tents

IP 54

1) 11)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Hallenspiegelleuchten: Mirona Fit⋅⋅⋅

Lamps that are - in the traffic area of the audience - located at a height of 2 m above the floor must be equipped with a protection against breaking due to mechanical stress.

Exhibition rooms

IP20

1) 8) 12)

Based on photometric requirements

Emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”)

Exterior areas, exposed to rain

IPx3

1) 2) 9)

Outdoor luminaires, Weather-proof luminaires: (restricted, in accordance with the product documentation): Duroxo⋅⋅⋅, Nextrema⋅⋅⋅

Exterior areas, ramps (covered)

IPx1

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Downlights: Inperla Ligra Plus (with cover), Continuous-line luminaires: E-Line IP54⋅⋅⋅

Limit glare while loading.

F

Factory farming

IP44

1) 3) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅

In case dust occurs IP54, consider ammonia resistance (see chapter “Chemical safety” ).

Feed kitchens (agricultural facilities)

IP44

1) 2) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washer: IPx9, consider ambient temperature.

Feed processing (agricultural facilities)

IP44

1) 2) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅

In case dust occurs: IP54. Where applicable, premises posing a fire hazard.

Fertilizer shed

IP44

1) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

In case dust occurs IP54, where applicable, premises posing a fire hazard. Where applicable, adhere to explosion protection.

Film screening rooms (audience)

IP20

1) 10) 12)

Wall-mounted luminaires, Downlights, Accent luminaires

Accent lighting increases the perceived value of the lighting. Emergency lighting of escape routes for 3 hour length of operation, where applicable anti-panic lighting (also see Chapter “Emergency lighting”).

Food processing, drying

IPx1

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard. Protection against mechanical damage (breakage of glass) in the processing area is required.

Food processing, fermenting, pressing/squeezing

IPx1

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, protection against mechanical damage (breakage of glass) in the processing area is required.

Food processing, general

IP20

1)

Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, take hygiene regulations into consideration, protection against mechanical damage (breakage of glass) in the processing area is required.

Food processing, slaughtering

IPx1

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, take hygiene regulations into consideration, protection against mechanical damage (breakage of glass) in the processing area is required.

Freight forwarding operations

IP20

1)

Continuous-line luminaires: E-Line⋅⋅⋅

In case dust occurs IP50

G

Galvanic facilities

IPx4

1) 2)   12)

Weather-proof luminaires, High bay luminaires: on request

Cleaning with jet water: IPx5, with pressure washer: IPx9, plan safety lighting for workspaces with particular hazards (also see chapter “Emergency lighting”).

Garages, car parks, underground car parks

IPx1

1) 12)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Gas stations, roofed over

IPx1

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Mirona Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Gateways

IPx3

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Limit glare while loading

Granaries

IP54

1) 3) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Premises posing a fire hazard. Where applicable, adhere to explosion protection.

Greenhouses

IPx4

1) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, High bay luminaires: Mirona Fit⋅⋅⋅

In case dust occursIP54, cleaning with jet water: IPx5, with pressure washers: IPx9.

Gymnasium and sports halls

IP20

1) 13)

Ball-proof luminaires: Actison⋅⋅⋅

Ball-impact-resistant luminaires (see Chapter “Mechanical safety”). In case of radiant ceiling heating system, further inquiry required.

H

Hosiery factory

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Hotel rooms

IP20

1)

Downlights: Inplana⋅⋅⋅, Onplana⋅⋅⋅, Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅) , Wall-mounted luminaires (z. B. Polaron IQ⋅⋅⋅, Accent luminaires

Comfortable lighting very important, utilise accent lighting, brightness control recommended.

I

Industrial halls

IP20

1)

Continuous-line luminaires: E-Line⋅⋅⋅, C-Line⋅⋅⋅, Coriflex⋅⋅⋅, High bay luminaires: Mirona Fit⋅⋅⋅

In case dust occurs: IP50. In the hand area diffuser luminaires and/or lamps with protective tubing, zonal lighting in case of high light levels through suspended luminaires, in case of special environmental conditions (temperature, humidity, aggressive media, etc.) utilise corresponding luminaires.

K

Kitchens, commercial kitchens

IPx4

1) 2)

Weather-proof luminaires: Fidesca BS⋅⋅⋅, Nextrema⋅⋅⋅, Aragon⋅⋅⋅, 713⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, consider ambient temperature, in case of cleaning with aggressive cleaning agents, consider chemical resistance (see Chapter “Chemical safety” ).

Kitchens, feed kitchens (agricultural facilities)

IP44

1) 3) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, consider ambient temperature.

Kitchens, sculleries

IPx4

1) 2)

Weather-proof luminaires: Fidesca BS⋅⋅⋅, Nextrema⋅⋅⋅, Aragon⋅⋅⋅, 713⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, consider ambient temperature, in case of cleaning with aggressive cleaning agents, consider chemical resistance (see Chapter “Chemical safety” ).

L

Laboratories

IP 20

1)

504⋅⋅⋅, 3331⋅⋅⋅, Arimo Slim D CDP⋅⋅⋅, Fidesca SD⋅⋅⋅

In case dust occurs: IP50. In the hand area diffuser luminaires and/or lamps with protective tubing, if applicable, take chemical resistance into consideration (see Chapter “Chemical safety” ), in case of VDU workspaces consider luminance limitation.

Laundry rooms/facilities

IPx1

1) 2)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Leather processing

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Weather-proof luminaires: hrefhttp://www.trilux.com/TOC/NEXTREMAG3Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Livestock breeding, ancillary rooms

IP44

1) 6)

Weather-proof luminaires: hrefhttp://www.trilux.com/TOC/DUROXODuroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

In case dust occurs: IP54. Where applicable, premises posing a fire hazard. consider ammonia resistance (see chapter “Chemical safety” ).

Livestock breeding, intense

IP44

1) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅

In case dust occurs: IP54. Where applicable, premises posing a fire hazard. Consider ammonia resistance (see chapter “Chemical safety” ).

M

Meat and fish processing processing plants

IPx5

1) 2) 12)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, in case of cleaning with aggressive cleaning agents, consider chemical resistance (see Chapter “Chemical safety” ). Plan safety lighting for workspaces with particular hazards.

Milk chambers (agriculture)

IP44

1) 6)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Milking parlours

IP44

1) 6)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Mobile constructions, event tents, event booths

IP 54

1) 11) 12)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, High bay luminaires: Mirona Fit⋅⋅⋅

Lamps that are - in the traffic area of the audience - located at a height of 2 m above the floor must be secured with a protection against breaking due to mechanical stress. Emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”)

Motor vehicle washing rooms

IP54

1) 2)

Weather-proof luminaires: Duroxo⋅⋅⋅

Direct contact of the luminaire with cleaning agents can lead to embrittlement of diffuser fasteners, etc., cleaning with jet water: IPx5, with pressure washers: IPx9, consider ambient temperature.

Museums

IP20

1) 8) 10) 12)

Based on photometric requirements

Lighting planning is very particular, mostly accent lighting. Emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Music schools, concert halls

IP20

1) 10) 12)

Diffuser luminaires: 3331⋅⋅⋅, Polaron IQ⋅⋅⋅

Take noise level into consideration, luminaire louvres and loose components as well as ceiling components can be excited into resonance vibrations, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

N

Non-woven fabric and wadding processing

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

O

Offices

IP20

1)

Diffuser luminaires: Arimo Slim CDP⋅⋅⋅, Belviso Active⋅⋅⋅, louvre luminaires: Arimo Slim MRX⋅⋅⋅, Work zone luminaires, if applicable: Bicult⋅⋅⋅, Belviso S⋅⋅⋅, Offset S⋅⋅⋅, Lateralo⋅⋅⋅, Luceos Slim⋅⋅⋅, Lunexo⋅⋅⋅, Parelia⋅⋅⋅

In case of VDU workspaces consider luminance limitation, light accents increase the perceived value of the lighting.

Operating rooms, general lighting

IP20

1) 7)

Cleanroom luminaires: Fidesca PM⋅⋅⋅, Fidesca SD⋅⋅⋅

For reasons of hygiene, IP54 and/or IP65 are recommended, when cleaning with aggressive cleaning agents, consider chemical resistance (see Chapter “Chemical safety” ), consider compatibility with IR control systems (e.g. OR table control, see Chapter “Compatibility with IR remote controls”)

Outdoor storage areas for hay, straw (roofed over)

IP54

1) 3) 6)

Weather-proof luminaires: Nextrema⋅⋅⋅, Duroxo⋅⋅⋅, Duroxo⋅⋅⋅, Aragon⋅⋅⋅, 713⋅⋅⋅, Oleveon Fit⋅⋅⋅

Premises posing a fire hazard.

P

Paper processing facilities

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Pig-fattening farms

IP54

1) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅

Premises posing a fire hazard. consider ammonia resistance (see chapter “Chemical safety” ).

Plastic fibre processing

IP50

1) 3) 4)

Diffuser luminaires: 3331⋅⋅⋅, Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Platforms, not roofed over

IPx3

1) 2) 9)

Outdoor luminaires

Cleaning with jet water: IPx5, with pressure washers: IPx9, limit glare.

Platforms, roofed over

IPx1

1) 2) 9)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, limit glare.

Premises posing a fire hazard

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Public areas

IP 20

1) 10) 12)

Wall-mounted luminaires (z. B. 3331⋅⋅⋅, Deca⋅⋅⋅, Polaron IQ⋅⋅⋅, 74R⋅⋅⋅, 74Q⋅⋅⋅, Downlights: Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅, Inplana⋅⋅⋅, Onplana⋅⋅⋅, Accent luminaires

In case of VDU workspaces consider luminance limitation, light accents increase the perceived value of the lighting, possibly lighting with colour-changing dynamics, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Pump rooms

IPx1

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Duroxo⋅⋅⋅, Aragon⋅⋅⋅, 713⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

R

Reading halls

IP20

1) 10) 12)

Diffuser luminaires: Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Arimo Slim⋅⋅⋅, Free-standing luminaires: Belviso S⋅⋅⋅, Offset S⋅⋅⋅, Work zone luminaires: Bicult⋅⋅⋅, Lateralo⋅⋅⋅, Luceos Slim⋅⋅⋅, Parelia⋅⋅⋅

Take noise level into consideration, avoid reflectice glare on reading areas and VDUs, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

S

Salesrooms (business premises)

IP20

1) 12)

Downlights: Inplana⋅⋅⋅, Onplana⋅⋅⋅, Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅, Diffuser luminaires: Arimo Slim MRX ⋅⋅⋅, Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Belviso Active⋅⋅⋅, Accent luminaires

In case dust occurs: IP50. In case of VDU workspaces consider luminance limitation, consider increased requirements of colour rendering, where applicable. Light accents increase the perceived value of the lighting, possibly lighting with colour-changing dynamics, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Sanitary rooms

IP20

1) 2) 4)

Downlights, Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅, Diffuser luminaires: Acuro⋅⋅⋅, Solvan Flow C⋅⋅⋅, Weather-proof luminaires

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Sawmills

IP50

1) 3) 12)

Diffuser luminaires: 3331⋅⋅⋅, Weather-proof luminaires: Nextrema⋅⋅⋅, Duroxo⋅⋅⋅, Aragon⋅⋅⋅, 713⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard, plan safety lighting for workspaces with particular hazards (also see chapter “Emergency lighting”).

Schools

IP20

1) 10) 12)

Diffuser luminaires: 3331⋅⋅⋅, Solvan Flow C⋅⋅⋅, Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Belviso Active⋅⋅⋅, Arimo Slim CDP ⋅⋅⋅, Luceos Slim⋅⋅⋅, Lunexo⋅⋅⋅

Consider glare limitation. Plan for lighting for blackboard (also see Chapter “Lighting of educational facilities”). Emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Schools, blackboard

IP 20

1)

Louvre and diffuser luminaires: 504⋅⋅⋅

Utilise luminaires with asymmetrical or narrow-angle light distribution, consider glare limitation.

Schools, special-subject classrooms

IP20

1)

Diffuser luminaires: 3331⋅⋅⋅, Solvan Flow C⋅⋅⋅, Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Belviso Active⋅⋅⋅, Arimo Slim CDP ⋅⋅⋅, Luceos Slim⋅⋅⋅, Lunexo⋅⋅⋅

Consider glare limitation. Plan for lighting for blackboard and experiment table (also see Chapter “Lighting of educational facilities”), vorsehen. Emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Showers and bathrooms, general

IP20

1) 4)

Diffuser luminaires: 3331⋅⋅⋅, Acuro⋅⋅⋅, Solvan Flow C⋅⋅⋅, Polaron IQ⋅⋅⋅, Arimo Slim CDP⋅⋅⋅

Outside zones 0, 1 und 2.

Showers and bathrooms, zone 0

IPx7

1) 4)

Cleaning with pressure washers: IPx9.

Showers and bathrooms, zone 1

IPx4

1) 4)

LED luminaires, protection class III

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Showers and bathrooms, zone 2

IPx4

1) 4)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Special-subject classrooms

IP20

1)

Diffuser luminaires: 3331⋅⋅⋅, Solvan Flow C⋅⋅⋅, Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Belviso Active⋅⋅⋅, Arimo Slim CDP ⋅⋅⋅, Luceos Slim⋅⋅⋅, Lunexo⋅⋅⋅

Consider glare limitation.

Sports and gymnasium halls

IP20

1) 13)

Ball-proof luminaires: Actison⋅⋅⋅

Ball-impact-resistant luminaires (see Chapter “Mechanical safety”). In case of radiant ceiling heating system, further inquiry required.

Squash courts

IP20

1) 13)

Ball-proof recessed diffuser luminaires: Actison⋅⋅⋅ with PMMA cover

Closed luminaires, ball-impact-resistant (see Chapter “Mechanical safety”). Consideration special luminaire placement. In case of radiant ceiling heating system, further inquiry required.

Stables for large and small animals

IP44

1) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, others on request

In case dust occurs: IP54. Where applicable, premises posing a fire hazard. Consider ammonia resistance (see chapter “Chemical safety” ).

Stables, ancillary rooms

IP44

1) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

In case dust occurs: IP54. Where applicable, premises posing a fire hazard. Consider ammonia resistance (see chapter “Chemical safety” ).

Stables, breeding rooms

IP44

1) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, others on request

In case dust occurs: IP54. Where applicable, premises posing a fire hazard. Consider ammonia resistance (see chapter “Chemical safety” ).

Staircases, corridors

IP20

1) 12)

3331⋅⋅⋅, Downlights, Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅, Inplana⋅⋅⋅, Onplana⋅⋅⋅, Wall-mounted luminaires: 74R⋅⋅⋅, 74Q⋅⋅⋅, 748⋅⋅⋅, Deca⋅⋅⋅, Polaron IQ⋅⋅⋅

Avoid glare and irritations at stairs through lighting, LED luminaires preferred (in particular in case of automatic switching systems with short operating duration)

Storage rooms, general

IP 20

1)

Continuous-line luminaires: E-Line⋅⋅⋅, C-Line⋅⋅⋅

Protection rating dependent on stored goods, in case dust occurs: IP50. In case of VDUs avoid reflex formation

Storerooms for bed feathers

IP50

1) 3)

Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Storerooms for feed, fertilizer

IP44

1) 3) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Premises posing a fire hazard. Where applicable, adhere to explosion protection.

Storerooms for grain

IP54

1) 3) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Premises posing a fire hazard.

Storerooms for hay, straw, jute, flax

IP54

1) 3) 6)

Continuous-line luminaires: E-Line IP54⋅⋅⋅, Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Premises posing a fire hazard.

Storerooms for raffia products, reed, and reed products

IP50

1) 3)

Continuous-line luminaires: E-Line IP54⋅⋅⋅, Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Premises posing a fire hazard.

Storerooms for rags

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Storerooms for sugar beet pulp (pellets)

IP50

1) 3)

Diffuser luminaires:3331⋅⋅⋅, Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Storerooms for wood chips

P50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Weather-proof luminaires:Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Swimming baths

IPx4

1) 2)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Swimming pool, Zone 0

IPx8

1) 2) 5)

Take chemical resistance into consideration, Zone 0 specialty luminaires required.

Swimming pool, Zone 1

IPx4

1) 2) 5)

LED luminaires, protection class III

Cleaning with jet water IPx5, special luminaires required. Take chemical resistance into consideration in areas with an atmosphere containing chlorine (see chapter “Chemical safety” , luminaires on request).

Swimming pools, general

IP20

1) 5) 10) 12)

Wall-mounted luminaires: 3331⋅⋅⋅, Deca⋅⋅⋅, Polaron IQ⋅⋅⋅, 74R⋅⋅⋅, 74Q⋅⋅⋅, Downlights: Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅, Inplana⋅⋅⋅, Onplana⋅⋅⋅, Accent luminaires

Light accents increase the perceived value of the lighting, possibly lighting with colour-changing dynamics, take chemical resistance into consideration in areas with an atmosphere containing chlorine (see chapter “Chemical safety” , luminaires on request).

T

Tablets, blackboards

IP20

1)

Louvre and diffuser luminaires: 504⋅⋅⋅

Utilise luminaires with asymmetrical or narrow-angle light distribution, consider glare limitation.

Teller windows, banks

IP20

1) 12)

Diffuser luminaires:Arimo Slim CDP⋅⋅⋅, Arimo Sky⋅⋅⋅, Belviso Active⋅⋅⋅, Arimo Slim MRX⋅⋅⋅, Work zone luminaires, if applicable : Belviso S⋅⋅⋅, Offset S⋅⋅⋅, Lateralo⋅⋅⋅, Luceos Slim⋅⋅⋅, Lunexo⋅⋅⋅, Parelia⋅⋅⋅, Bicult⋅⋅⋅

In case of VDU workspaces consider luminance limitation. Light accents increase the perceived value of the lighting, possibly lighting with colour-changing dynamics, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Tennis halls

IP20

1) 13)

Ball-proof luminaires: Actison⋅⋅⋅

Ball-impact-resistant luminaires (see Chapter “Mechanical safety”). Consider special luminaire placement. In case of radiant ceiling heating system, further inquiry required.

Tents, event tents

IP54

1) 11)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Hallenspiegelleuchten: Mirona Fit⋅⋅⋅

Lamps that are - in the traffic area of the audience - located at a height of 2 m above the floor must be equipped with a protection against breaking due to mechanical stress

Textile processing

IP50

1) 3)

Diffuser luminaires

Premises posing a fire hazard.

Theatre workshops

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Theatres

IP20

1) 10) 12)

Wall-mounted luminaires: 3331⋅⋅⋅, Deca⋅⋅⋅, Polaron IQ⋅⋅⋅, 74R⋅⋅⋅, 74Q⋅⋅⋅, Downlights: Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅, Inplana⋅⋅⋅, Onplana⋅⋅⋅, Accent luminaires

Light accents increase the perceived value of the lighting. Emergency lighting of escape routes for 3 hour length of operation, anti-panic lighting (also see Chapter “Emergency lighting”)

Treatment and examination rooms for ECG/EEG, and EMG measurements

IP20

1) 7)

Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Belviso Active⋅⋅⋅, Arimo Slim CDP ⋅⋅⋅, Arimo Sky⋅⋅⋅

Illumination level and light colour differing dependent on the type of examination, where applicable dimmable luminaires, in case of VDU workspaces, consider luminance limitation.

U

Underground parking garages, garages, large parking garages

IPx1

1) 12)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Underground railway stations

IPx1

1) 2) 12)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅

Limit glare, cleaning with jet water: IPx5, with pressure washers: IPx9, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Upholstery

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

V

VDU workspaces

IP20

1)

Work zone luminaires, if applicable (see Offices)

Consider luminance limitation.

W

Warehouses

IP20

1) 12)

Downlights, Inperla Ligra⋅⋅⋅, Athenik Ligra⋅⋅⋅, Accent luminaires, Diffuser and louvre luminaires: Arimo Slim MRX ⋅⋅⋅, Belviso C⋅⋅⋅, Belviso D⋅⋅⋅, Belviso Active⋅⋅⋅

In case dust occurs: IP50. In case of VDU workspaces consider luminance limitation, consider increased requirements of colour rendering, where applicable. Light accents increase the perceived value of the lighting, possibly lighting with colour-changing dynamics, emergency lighting of escape routes for 3 hour length of operation (also see Chapter “Emergency lighting”).

Washing facilities – automobile

IP54

1) 2)

Weather-proof luminaires: Nextrema⋅⋅⋅, Duroxo⋅⋅⋅

Direct contact of the luminaire with cleaning agents can lead to embrittlement of diffuser fasteners etc. (see chapter “Chemical safety” ), Cleaning with jet water: IPx5, with pressure washers: IPx9, consider ambient temperature.

Weaving plant

IP50

1) 3)

Diffuser luminaires: 3331⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard.

Wet workshops, e.g. stone working

IPx4

1) 2) 6)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Wine and beer cellars

IPx1

1) 2)

Weather-proof luminaires: Duroxo⋅⋅⋅, Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Cleaning with jet water: IPx5, with pressure washers: IPx9.

Wood flour processing

IP50

1) 3)

3331⋅⋅⋅, Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard. Where applicable, adhere to explosion protection.

Wood working

IP50

1) 3) 12)

3331⋅⋅⋅, Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅, 748⋅⋅⋅, Continuous-line luminaires: E-Line IP54⋅⋅⋅

Premises posing a fire hazard, plan safety lighting for workspaces with particular hazards (also see chapter “Emergency lighting”).

Workshops – automobile

IP20

1) 12)

Weather-proof luminaires: Nextrema⋅⋅⋅, Araxeon⋅⋅⋅, Aragon⋅⋅⋅, Oleveon Fit⋅⋅⋅ Continous-line luminaires: E-Line⋅⋅⋅, C-Line⋅⋅⋅, Coriflex⋅⋅⋅

In case of cleaning with jet water: IPx5, with pressure washers: IPx9. Stand-by lighting must be planned for in case of workspaces with particular hazards (also see Chapter “Emergency lighting”). In case of contact with fats and oils, luminaire covers made of PMMA are recommended.

1.
HD 60364-5-559, Low-voltage electrical installations - Part 5-559: Selection and erection of electrical equipment - Luminaires and lighting installations
2.
DIN VDE 0100-737, Erection of low-voltage installations - Humid and wet areas and locations, outdoor installations
3.
HD 60364-4-42, Low voltage electrical installations - Part 4-42: Protection for safety - Protection against thermal effects
4.
HD 60364-7-701, Low-voltage electrical installations - Part 7-701: Requirements for special installations or locations - Locations containing a bath or shower
5.
DIN VDE 0100-702, Low-voltage electrical installations - Part 7-702: Requirements for special installations or locations - Basins of swimming pools, other water basins and fountains
6.
HD 60364-7-705, Low-voltage electrical installations - Part 7-705: Requirements for special installations or locations - Agricultural and horticultural premises
7.
HD 60364-7-710, Low-voltage electrical installations - Part 7-710: Requirements for special installations or locations - Medical locations
8.
prHD 60364-7-711, Low voltage electrical installation - Part 7-711: Requirements for special installations or locations - Exhibitions, shows and stands
9.
HD 60364-7-714, Low-voltage electrical installations - Part 7-714: Requirements for special installations or locations - External lighting installations
10.
HD 60364-7-718, Low-voltage electrical installations - Part 7-718: Requirements for special installations or locations - Communal facilities and workplaces
11.
prHD 60364-7-722, Low-voltage electrical installations - Part 7-722: Requirements for special installations or locations - Supplies for electric vehicles
12.
EN 50172, Emergency escape lighting systems
13.